6-6 Analog Input Functional Block
All fields on this tab will be disabled if the Translation Enabled option is not set
on the
Analog Input tab.
Output Parameters
This tab appears as follows:
This tab determines how often data is sent on the Analog network variable and
the minimum, maximum, and override values. This tab contains the following
fields:
Minimum Value The minimum value that will be sent by the output
network variable. If this limit is exceeded the output
will be clipped at this limit.
Maximum Value The maximum value that will be sent by the output
network variable. If this limit is exceeded the output
will be clipped at this limit.
Send on Delta The sensed value must change by at least this
amount before a new value is sent. A new value will
still be sent if the heartbeat time expires.
Override The value that will be sent by the
Analog output
network variable if this functional block is put into
override.