The LonPoint Application and Plug-in Guide 10-39
Manually Entering Time and Date
You can manually change either the time or date in the simulator in order to
verify operations at future times/dates. Whenever either field is manually
changed, the simulator will automatically perform a reset by backing up twenty-
four hours for the new time/date and fast forwarding to the new time/date while
simulating all events in the last twenty-four hours in order to get the state
machine in a state that is current relative to the new date and time.
Overriding the Event Schedule
The Current Schedule field indicates what daily schedule is currently being
used. You can manually set the schedule by clicking on the
Manual Schedule
button and selecting the desired schedule from the current schedule list. This
allows you see the behavior of all daily schedules without waiting for every daily
schedule to become active based on the simulated day or date.