5-6 Digital Encoder Functional Block
To create a table that sends an HVAC_EMERG_HEAT mode on the Mode_Out
network variable if any of the four inputs are On and HVAC_AUTO if they are
all Off, you would set the
Mode Output column to HVAC_EMERG_HEAT in all
the rows but the first (in which at least one of the four inputs has a value of 1)
and to HVAC_AUTO in the first row (where all four inputs are 0), as follows: