i.LON 100 Internet Server User’s Guide 4-19
The options on this page are divided into LonTalk Properties, NVE Driver
Properties, LNS Uplink/Downlink Properties, and Initiate LNS Uplink
Properties. These properties are discussed in the following sections:
Configuring LonTalk Properties
The following LonTalk properties are shown:
Neuron ID Range The range of Neuron IDs used by the i.LON 100.
This field is read-only.
Channel Type The LonWorks Channel type supported by the
i.LON 100. This is TP/FT-10 for FT model i.LON
100s and PL-20N (or PL-20C if CENELEC is
enabled) for PL model i.LON 100s.
Domain/Subnet/Node If the i.LON 100 is configured (i.e. it has been
added to an LNS network), this field displays the
Domain/Subnet/Node address of the i.LON 100.
Otherwise, this field will display Unconfigured.
By default, this field is read-only; check the
Modify? option to make this field writable. Note
that modifying the Domain/Subnet/Node address
of the i.LON 100 may make it inaccessible by the
LNS network.
CENELEC Enable This option only appears if you have a power-line
model i.LON 100. Set this option to enable
CENELEC power-line communication. If you
change this value, you will need to close all
applications to which the i.LON 100 is connected