2-16 Mounting, Cabling and Connections
i.LON 100 Server L
ONWORKS TP/FT-10 Free Topology
Twisted Pair Terminals
i.LON 100 Server L
ONWORKS TP/FT-10 Network Connections
Screw Terminal Enclosure Marking L
ONWORKS Network
Connection
17 LON B TP/FT-10 twisted pair
18 LON A / PLT Tap TP/FT-10 twisted pair
+12V < 20mA Output
The i.LON 100 server is provided with one +12V outlet that can provide up to
20mA. This +12VDC connection may be used by a set of dry contacts to power
the optically isolated digital inputs.
The +12V <20mA output is implemented on screw terminals 19 and 20. Screw
terminal 20 is the +12 Volt power connector. Screw terminal 19 is the system
ground.
i.LON 100 Server L
ONWORKS +12V < 20mA Output Terminals