2-8 Mounting, Cabling and Connections
Safety Warning
When connecting a unit, always connect earth ground first, then Neutral,
then Line. This minimizes the risk of shock or damage should power
inadvertently be present on Line.
!
Safety Warning
Fuse F350 in the i.LON 100 server uses a Wickmann rated 250 VAC, .5 A,
SLO-BLO.
!
Safety Warning
The i.LON 100 server uses a Poly-carbonmonoflouride Lithium Coin battery.
CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN
INCORRECT TYPE.
DISPOSE OF UNUSED BATTERIES ACCORDING TO THE
INSTRUCTIONS.
!
Safety Warning
The i.LON 100 server is not equipped with a power disconnect device. When
the device is installed and mounted, the installer must provide a means to
safely remove power, such as a power-switch or a circuit-breaker.
!
Safety Warning
The high-voltage terminal block has a plastic cover protecting the screw
terminals used to connect the high-voltage inputs. This cover MUST be
replaced after the power wires are connected and before the power is
activated.
The 100-240VAC power mains connection is used to both power the i.LON 100
Internet Server and, in the case of the power line models (Models 72103 and