I/O Model Reference 119
IO10
IO9
IO8
IO0
IO1
IO2
IO3
IO4
IO5
IO6
IO7
Optional Pull-Up Resistors
(3100 Family Only)
IO11
t
dw
DATA
A
START OF
io_in()
END OF
io_in()
DATA
B
TIMEOUT
TIME
t
ibd
t
fin
t
tow
t
tret
t
ret
Figure 45. Wiegand Input and Timing
Table 47. Wiegand Input Latency Values for Series 3100 Devices
Symbol Description Minimum Typical Maximum
t
fin
Function call to start of second data edge 75.6 μs —
t
dw
Input data width (at 10 MHz) 200 ns 100 μs 880 ms
t
ibd
Inter-bit delay 150 μs — 900 μs
t
low
Timeout pulse width 39 μs —
t
tret
Timeout to function return 18.0 μs —
t
ret
Last data bit to function return 74.4 μs —